Accuracy (+ or - 0.2% RO) |
 |
Excellent long term
stability (4-20ma, 500 ohm) |
 |
Precision
measurement even for distorted wave (S3-AD-1T) |
 |
High Impulse &
surge protection (5KV) |
 |
The case
can be mounted on a 35mm rail which complies with DIN 46277 |
|
Sinusoidal Waveforms - AVG
S3-AD Series
Transducer converting a sinusoidal alternating voltage into a dc output,
proportional to the RMS value of input. These units are average sensing, but
RMS
calibrated for a sine wave with less than 1% distortion. The input signal
is converted
to a dc voltage which then feeds to a single amplifier and a dc
output produced.
|
|

|
|
Non-Sinusoidal Waveforms - TRMS
S3-AD-1T Transducer are designed for use on waveforms with up to 30% of
3rd
harmonic content. The input signal is fed to an RMS detection circuit
and the
resultant dc volts produced are a linear function of the RMS value
of input
waveform. This dc voltage is converted to a milliamp output via an
output
amplification circuit.
|
|

|
|
Input-Output Curve
|
|

|
|
SPECIFICATIONS
|
|
Input
|
|
Input
Range |
Input
Burden |
Input
Frequency |
Max.
Input
Over Capability
|
|
0-5A |
<
0.2VA
|
50Hz (+ or -) 3Hz
or
60Hz (+ or -) 3Hz
|
3
x rated continuous
10 x rated 10 sec.
50 x rated 1 sec. |
|
0-10A |
|
Output
|
|
DC Output Range |
Load
Resistance |
Output
Resistance |
Output
Ripple |
Response
Time |
|
0-1V |
> 1K Ohm |
< 0.05 Ohm |
< 0.5% RO
(Peak) |
< 400mS
0-99% |
|
0-5V |
|
1-5V |
|
0-10V |
|
0-1mA |
0-10K Ohm |
> 20M Ohm |
|
0-10mA |
0-1K Ohm |
|
|
0-20mA |
0-500 Ohm |
0-500 Ohm |
|
4-20mA |
|
| Accuracy |
+ or - 0.2% rated of
Output |
| Aux. power
supply |
AC 110V (+
or -) 15%, 50/60 Hz
AC 220V (+ or -) 15%, 50/60 Hz
DC 24V, 48V, 110V, (+ or -) 15%
|
| Power
consumption |
(<) 2.5VA,
(+ or -) DC 3W |
| Power effect |
(<) 0.% RO |
| Waveform
effect |
(<) 0.2% RO
at distortion factor 30%
(S3-AD-1T) |
| Output load
effect |
(<) 0.05% RO |
| Magnetic
field strength |
(<) 0.2% RO,
400 A/M |
| Span
adjustment |
(>) 5% RO |
| Zero
adjustment |
(>) 1% RO |
| Operating
temperature range |
0-60 degrees
C |
| Storage
temperature range |
(-) 10-70
degrees C |
| Temperature
coefficient |
(<) 100PPM
from 0-60 deg. C
(<) 60 PPM, 25 deg. C (+ or -) 10 deg. C |
| Max.
relative humidity |
95% |
| Isolation |
Input/Output/Power/Case |
| Insulation
resistance |
(>) 100M
ohm, DC 500V |
Dielectric
withstand voltage
(IEC 414, 688, ANSI, C37) |
Between
input/output/power/case
ac 2.5kv, 60Hz, 1 min |
Impulse
withstand test
(IEC 255-4, ANSI, C37 90) |
5 kv, 1.2 x
50 nS
common mode & differential mode |
| Performance |
Designed to
comply with IEC688 |
| Safety
requirements |
IEC 414,
BS5458 |
|
|
Back to
Transducers
|