Active Power/Watt Transducers
|
|
|
DESCRIPTION
Model: S3-WD-1 - Single Phase 2 W, active power (WATT)
S3-WD-3 - Three Phase 3 W, active power (WATT)
S3-WD-3A- Three Phase 4 W, active power (WATT)
A wide range of transducers to measure all forms of active power, in both balanced
and unbalanced, single or 3 phase system. They utilize the well prove "time division
multiplication" method of measuring instantaneous power over a wide range of input
waveforms. The circuit diagram shown measured voltage is modulated by circuit of
an oscillator. Square wave pulses from a multi-vibrator circuit, with a mark-space ratio
varied by the measured voltage and amplified by the measured current, are fed to an
integrator an output amplification circuit. The dc signal produced is then directly
proportional to power input-Watts.
|
SPECIFICATION INPUT
| |
Input Range |
Max.
Input
Over Capability |
|
Circuit |
Amp |
Voltage |
Basic Watt |
Ampere:
3 x rated continuous
10 x rated 10 sec.
50 x rated 1 sec.
Voltage:
480V |
|
Single Phase |
5 Amp |
110V(120V)
220V(240V) |
0-0.5KW
0-1KW |
|
Three Phase |
5 Amp |
110V(120V)
220V(240V) |
0-1KW
0-2KW |
|
Three Phase
|
5 Amp |
190/110V
(208/120V) |
0-1.5KW |
|
|
DC Output Range |
Load
Resistance |
Output
Resistance |
Output
Ripple |
Response
Time |
|
0-1V |
> 1K Ohm |
< 0.05 Ohm |
< 0.5% RO
(Peak) |
< 400mS
0-99% |
|
0-5V |
|
1-5V |
|
0-10V |
|
0-1mA |
0-10K Ohm |
> 20M Ohm |
|
0-10mA |
0-1K Ohm |
|
|
0-20mA |
0-500 Ohm |
0-500 Ohm |
|
4-20mA |
|
|
Accuracy |
+ or - 0.2% rated of Output |
|
Input Frequency |
50Hz (+ or -) 3Hz or 60Hz (+ or -) 3Hz |
|
Input Burden |
<0.1VA (ampere input)
< 0.2VA (voltage input) |
|
Aux. power supply |
AC 110V (+ or -) 15%, 50/60 Hz
AC 220V (+ or -) 15%, 50/60 Hz
DC 24V, 48V, 110V, (+ or -) 15%
|
|
Power consumption |
(<) 4VA, < DC 3W |
|
Power effect |
(<) 0.1% RO |
|
Waveform effect |
(<) 0.2% RO at distortion factor 15%
|
|
Output load effect |
(<) 0.05% RO |
Electromagnetic
Balance effect |
<0.1% RO |
|
Mutual Interference effect |
<0.1% RO between element |
|
Magnetic field strength |
(<) 0.2% RO, 400 A/M |
|
Span adjustment |
(>) 5% RO |
|
Zero adjustment |
(>) 1% RO |
|
Operating temperature range |
0-60 degrees C |
|
Storage temperature range |
(-) 10-70 degrees C |
|
Temperature coefficient |
(<) 100PPM from 0-60 deg. C
(<) 60 PPM, 25 deg. C (+ or -) 10 deg. C |
|
Max. relative humidity |
95% |
|
Isolation |
Input/Output/Power/Case |
|
Insulation resistance |
(>) 100M ohm, DC 500V |
Dielectric withstand voltage
(IEC 414, 688, ANSI, C37) |
Between input/output/power/case
ac 2.5kv, 60Hz, 1 min |
Impulse withstand test
(IEC 255-4, ANSI, C37 90) |
5 kv, 1.2 x 50 nS
common mode & differential mode |
|
Performance |
Designed to comply with IEC688
|
|
Safety requirements |
IEC 414, BS5458 |
|