AC Voltage Transducers
|
|
Features
|
|
DESCRIPTION
Model: S3-VD-1 - Single Phase input (AVG)
S3-VD-3 - Three Phase input (AVG)
S3-VD-1T - Single Phase input (TRMS)
|
|
|
Sinusoidal Waveforms - AVG
S3-VD Series Transducer converting a sinusoidal alternating voltage
into a dc output, proportional to the RMS value of input. These units are
average sensing, but RMS calibrated for a sine wave with less than 1%
distortion. The input signal is converted to a dc voltage which then feeds to a
single amplifier and a dc output produced.

Non-Sinusoidal Waveforms - TRMS
S3-VD-1T Transducer are designed for use on waveforms with up to 30%
of 3rd harmonic content. The input signal is fed to an RMS detection circuit and
the resultant dc volts produced are a linear function of the RMS value of input
waveform. This dc voltage is converted to a milliamp output via an output
amplification circuit.

Input-Output Curve

SPECIFICATION
Input
|
Input Range |
Input Burden |
Input Frequency |
Max. Input
Over Capability |
|
0-150V |
< 0.2VA
|
50Hz (+ or -) 3Hz
or
60Hz (+ or -) 3Hz
|
2 x rated continuous |
|
0-500V |
Output
| DC
Output Range |
Load
Resistance |
Output
Resistance |
Output
Ripple |
Response
Time |
| 0-1V |
> 1K Ohm |
< 0.05 Ohm |
< 0.5% RO
(Peak) |
< 400mS
0-99% |
| 0-5V |
| 1-5V |
| 0-10V |
| 0-1mA |
0-10K Ohm |
> 20M Ohm |
| 0-10mA |
0-1K Ohm |
|
| 0-20mA |
0-500 Ohm |
0-500 Ohm |
| 4-20mA |
| Accuracy |
+ or - 0.2%
rated of Output |
| Aux. power
supply |
AC 110V (+
or -) 15%, 50/60 Hz
AC 220V (+ or -) 15%, 50/60 Hz
DC 24V, 48V, 110V, (+ or -) 15%
|
| Power
consumption |
(<) 2.5VA,
(+ or -) DC 3W |
| Power effect |
(<) 0.% RO |
| Waveform
effect |
(<) 0.2% RO
at distortion factor 30%
(S3-AD-1T) |
| Output load
effect |
(<) 0.05% RO |
| Magnetic
field strength |
(<) 0.2% RO,
400 A/M |
| Span
adjustment |
(>) 5% RO |
| Zero
adjustment |
(>) 1% RO |
| Operating
temperature range |
0-60 degrees
C |
| Storage
temperature range |
(-) 10-70
degrees C |
| Temperature
coefficient |
(<) 100PPM
from 0-60 deg. C
(<) 60 PPM, 25 deg. C (+ or -) 10 deg. C |
| Max.
relative humidity |
95% |
| Isolation |
Input/Output/Power/Case |
| Insulation
resistance |
(>) 100M
ohm, DC 500V |
Dielectric
withstand voltage
(IEC 414, 688, ANSI, C37) |
Between
input/output/power/case
ac 2.5kv, 60Hz, 1 min |
Impulse
withstand test
(IEC 255-4, ANSI, C37 90) |
5 kv, 1.2 x
50 nS
common mode & differential mode |
| Performance |
Designed to
comply with IEC688 |
| Safety
requirements |
IEC 414,
BS5458 |
Back to