Series 35 Temperature Monitor
3 digit LED display - 0-200 degrees C
The Series 35 Temperature Monitor is
a solid state device used for the indication and alarm on the
6 RTD's embedded
in the 3
phase motor windings (2 ea/phase)
The temperature set points for alarm and shutdown
are located on the rear of the instrument. The
3 digit
temperature indicator is
mounted on the front panel
with a 5 pt. selector switch. The indicator reads
point
PT (#1 probe), which is selected as the
hottest point. A
selector switch and
pushbutton
allow the other 5 points to be read on the meter. The instrument can be
supplied with inputs for 3 wire RTD's or for shorter distance
between monitor
and motor.
2 wire RTD connections can be used, thus requiring
only 6 wires and one common (7
total) from meter to monitor vs 18 wires
for 3 wire
RTD system.
*Note: A
8 point model is available which
monitors the 6 winding RTD's
and also the two end bearings
These are
our most requested manuals for our
Series 35 Temperature Monitors
These require the Adobe Reader to
access.
Series 35
6 Point Monitor
Series 35 8 Point Monitor
Series 35 3 Wire Monitor
Instruction Manuals/Series 35 (6
Point)Temp. Monitor.pdf
Instruction Manuals/Series 35 (8 Point)
Temp. Monitor.pdf
Instruction Manual/Series 35 (3 Wire) Temp_Monitor.pdf

SMART-2
Motor Bearing/Winding Temperature Monitor
This instrument is ideal for monitoring and
protection of a motor end bearing over-heating problem.
The controller input is from a 100 Ohm platinum RTD sensor
located at each of the end bearings. It has two relay
outputs which are used to provide the customer of an
over-heating alarm condition and a second adjustable relay which
is set at a higher temperature to provide a relay contact for
the customer to use to shut down the motor before damage to
bearings. One instrument is required for each of the two
card bearings. Price: $ 195.00 each.
Instruction Manual for SMART-2 Temperature Monitor
SMART-2
6 Point - Motor Winding
Temperature Monitor
This instrument is
available as a 6 point monitor for
panel mounting. All 6 points
with alarm/trip functions.
The case size is 9" x 9.75" x 8"
HWD with rear mount terminals for
customer connection of alarm and
trip relay contacts, power and 6
each 3 wire 100 ohm RTD's.
Part No. SMART-2-6A/T.
Price: $ 1620.00 each.

|
Model 15A-2 Alarm Controller
The Model 15A-2 Alarm Controller
Module operates either from a thermocouple RTD,
or other millivolt or milliamp input signal. The output is a 12
amp 120/240 VAC relay SPDT dry contacts. When used with
a thermocouple, burnout and automatic cold junction
compensation are standard. The alarm unit
consists of a
temperature stable D.C. amplifier, a driver stage and power
supply. The alarm/control point can be set either by means
of a dial located on
the top of the module or a remote dial
w/6ft.Cord. Standard dial ranges are
0-400, 0-1000, 0-2000
degrees F/degrees C. |
|
The standard alarm will provide a contact closure when the temperature (or
other input)
exceeds that set on the set point dial. The relay contacts (SPDT)
are brought out to the
customer connection terminals to be used for operation of
a remote control device i.e.
indicator light, annunciator, power relay, power
relay coil, shunt trip/breaker, etc.
The standard alarm is furnished with a
non-latching mode of operation, but it can
also be furnished as a latching alarm
w/reset pushbutton either located on the top of the
unit or at the customer
connection strip for remote reset pushbutton operation (N.C. contact).
In the non-latching mode of operation, the output relay contacts will
automatically return
to the normal condition when the temperature drops back
below the set point temperature.
In the latching mode, the output relay contacts
will remain in the alarm condition even when
the operating temperature drops
back below the set point temperature and must be reset by
depressing
momentarily, the reset pushbutton. The pushbutton is either furnished on the
module
or is connected to terminals provided on the customer connection strip
for a remote pushbutton
supplied by the customer.
FEATURES
* Solid State
Price:
$ 195.00
* Low Cost
* Remote or local potentiometer/dial
* w/or w/o LED Indication
* Cold Junction Compensation
* Open T.C. protection
* Thermocouple lead length not critical
SPECIFICATIONS
# Input - thermocouple (specify type and range)
# Optional - RTD, 4-20 ma millivolts DC voltage
# Output - SPDT relay 12 amps 250 VAC
# Latching or non-latching operation w/local or remote
pushbutton
Customer Connections
1. Connect 120 VAC 50, 60 Hz AC power to customer terminals labeled HOT-NEXT.
(120 VAC)
2. Connect Type K Chrome-Alumel thermocouple to customer terminals labeled
3. Connect the heater load to the Normally Open (N.O.) Relay contact. This is
customer connection labeled N.O. and C. relay contacts.
*Note: The N.O. contact is closed below control point wh the process is cold
and will open to remove power from the heater when temperature exceed that set
on the control temperature dial. The relay contacts are rated at 5 amps 120 VAC.
4. The remote set point dial is shipped with the cable connected to the
customer terminal strip W(red), CW(white), and CCW(black)
5. The unit is shipped with a jumper across the remote reset terminals (this
jumper must remain for normal controller operation).
The Model 15A-2 single point RTD alarm is designed to monitor Motor Winding
Temperature by means of resistance temperature detector (RTD).
The monitor utilizes a 100 ohm at 0 degrees C. RTD sensor in the motor
winding or end bearing surface. The RTD is connected to terminals labeled S0 and
S2. The terminals labeled P1, P2, and P3 are not used for this application, (
these are used when the alarm set point potentiometer is mounted on a plate for
remote mounting by customer ). The set point dial reads 0-200 degrees C. and is
set at the temperature desired to protect the motor. When the temperature
reaches the set or the dial, the relay will operate and the contacts at
terminals C, N.C. and N.O. will transfer, i.e., the contact labeled N.C. will
close, when the alarm set point is reached.
Also available for 10 ohm and 129 ohm RTD’S.
The Model 15A-2 Thermocouple Alarm is a low cost printed circuit module
furnished with dust cover and provisions for either the alarm trip point
adjustment on the unit or it can be located remotely with a separate dial and
potentiometer. The input can be from any type thermocouple and the output is a 5
amp 120 VAC relay. Thermocouple burnout protection and automatic cold junction
are standard features.
The alarm unit consists of a solid state integrated circuit and transformer
isolated power supply. The alarm unit will provide contact transfer at the
terminals labeled NC, NO, and C. The connection between NC and C will provide a
normally closed contact and between NO and C will provide a normally open
contact. The dead band between drop-in and drop-out of the relay contacts is
approximately 75-100 microvolts.
The 15A-2 alarm can be used either as a non latching ( auto-reset ) type of
alarm or a latching type of alarm, which must be reset with a NO pushbutton
contact ( momentary contact ) which is connected to terminals labeled RESET (
N.O.). With the latching mode used, the alarm unit will remain in the alarm
condition even though the thermocouple temperature drops back below that set on
the alarm set point adjustment dial. A jumper must be placed between the reset
terminals, if a non latching system is desired.
|
Dimensions: (1/4 DIN) 3 3/4" H
x 3 3/4" W x 3 1/8" D
Display: RTD Temperature - Red 0.56" H LED
Alarm Set Point Temperature: Green 0.4" H LED
Option - 4-20ma transmitter output for remote monitoring of
RTD temperature by PLC or computer


Instruction Manual for SMART-3 Temperature Monitor

Motor
Winding/Bearing
Monitor/Alarm
3 Alarm
Points
Over
Temperature
Alarm/Trip
Controller
Relay
Output
3 Each -
100 Ohm
RTD
Input
0-200
Deg. C
NEMA
Wallmount
Enclosure
Available
for 6
Point or
8 Points


Description
Of
Operation
The temperature monitor system consists of
a SMART-2 Digital
overtemp controller which has a relay
output at terminals #4 and #5
located on the rear of the
controller. This contact closes in an
over-temperature
condition which applies 120VAC to the 120VAC
coil of the
output relay, thus transferring the output relay contacts
to
a alarm condition.
If any one of the 3 temperature controllers
are in an alarm condition,
the output relay will be
placed in an alarm condition
and the alarm light for that particular point
will be lit.
The alarm temperature on the bottom digital
display (SV).
The desired value is entered on the display by
pressing the
Part No. SMART-2-3A/T
horizontal ²
keypad which will cause the digit to flash that will
Price: $ 1150.00
be entered
by use of up 8and down
9keypads. Press the horizontal
Note: Can also be supplied
keypad to flash the proper digit to be changed (press SET keypad
for thermocouple inputs
after numbers have been entered to store in memory)
The temperature of the RTD at the motor is
displayed on the upper
digital display (PV) Range 0-200 Degrees
C
*NOTE: This instrument
available as a 6 point Motor
Winding Monitor for panel
mounting. The case size is 9" x 9" x 9" HWD with rear
mount terminals for customer
connection of alarm and trip
relay contacts, power and 6
each 3 wire RTD's.
Part No. SMART-2-6A/T - Price:
$ 1620.00
Description of Operation
(Ref - Operating Flow Diagram)
Upper Display (PV) Displays the actual
temperature as measured by the RTD sensor
Lower Display (SV) Displays the alarm
temperature set point (preset at 90 Deg. C)
To observe the trip temperature Set Point
(AL1), press the SET key
until upper display shows AL1 and the
lower display will then indicate
the trip set point temperature
which is preset at 120 Deg. C. Continue
to press the SET key to
return to normal PV and SV display.
Customer Connections
Connect 120VAC power to TS-2 terminal strip located in bottom
of
panel and labeled 120V H and N
Connect
external alarm/trip circuit to output relay contacts located
on
terminal strip TS-2 and labeled C, N.C. and N.O. These are
dry relay contacts rated at 10
amps@120VAC and provide a normally
open or
normally closed contact for customer use.
Connect
the 100 Ohm platinum RTD's to terminal strip TS-1.
Connect the RTD for #1 point to terminals labeled
#1 and #2.
Terminal #3 is used for a 3 wire RTD. If
a 2 wire RTD is used,
no connection is
required to the 3rd terminal #3, 6, and 9.
#2 RTD is connected to terminals #4, 5, and 6
#3 RTD is connected
to terminals #7. 8, and 9

The Following products
are other applications for motor protection